¡á MCU&ASIC Based Compact Design
¡á Multiple Protection Functions
¡á Wide Voltage Adjustment Range
¡á Digital Volt Meter and Digital Setting
¡á Trip Cause Display & Troubleshooting
¡á Manual/Electrical/Automatic Reset
¡á Adjustable Reset Timer
¡á Ambient Insensitive
¡á Flush Mounting type
 
 
Protective Item

Trip Time

Over-voltage

0.5~10sec

Under-voltage
0.5~10sec
Phase Loss
2sec
Phase Reversal
0.1sec
Phase Unbalance
3sec(If over 5%)
   
 
 

Voltage Setting
Range

Type

Over-voltage(O-VOLT)

Under-voltage(U-VOLT)

110

110-150V

80-120V

220

220-300V

160-240V

440

380-500V

300-440V

Trip Time Setting Range

O-TIME

0.5 ~ 10sec

U-TIME
0.5 ~ 10sec

Control Voltage

220

85~250V AC/DC

Others
24,48VAC/DC(Optional Order)

Output Relay

Mode

1-SPDT(1C)

Rating
3A/250VAC Resistive

Status

Normally Energized
Reset
SW3=AUTO
Reset Time:1 or 5sec(DIP-SW4)
SW3=MAN
RESET Button

Mounting

FD
DCU
Flush
PCU
35mm DIN-Rail / Panel