¡á Compact Design
¡á Multiple Protection Functions
¡á Wide Current Adjustment Range(10:1)
¡á Ammeter Function
¡á Trip Indication LED
¡á High Accuracy
¡á Manual Instantaneous Reset
¡á Electrical Remote Reset
¡á Test Function
¡á Ambient Insensitive
¡á Low Power Consumption
¡á Fail-safe Operation(No Volt Release)
¡á Automatic Reset and Adjustable Reset Timer
 
 
Protective Item

Operating(Trip) Time

Over-current

O-TIME

Phase Loss
O-TIME
Locked Rotor
O-TIME
   
 
 

Current Setting

Type

Range

05

0.5 ~ 6A

30

3.0 ~ 30A

60

5.0 ~ 60A

over 60A

With External CT (CT ratio: 100/5A ~ 600/5A)

Time Setting

Trip
D-TIME

0.2 ~ 30sec

Reset
R-TIME
0.2 ~ 120sec

Control Voltage

220

90~260VAC

440
320 ~ 480VAC

Output Relay

Mode

1-SPDT(1C)

Rating
3A / 250VAC Resistive

Status

Normally Energized With Power
Time-Current Characteristic
Definite
Operating(Trip) Indication
LED

Mounting

35mm DIN-Rail / Panel