¡á  MCU( Microprocessor Control Unit ) Based/2-CT Type
¡á  Real Time Processing/Higher Preceision
¡á  Current Setting Range
05Type:0.5~6A/30Type:3~30A/60Type:10~60A
¡á  Indicating real current on the display
¡á  Trip cause digital display for easy trouble shooting
¡á  Reset:Manual(instantaneous)/Electrical(remote)
¡á  Load selection by DIP switch:Single phase(1P)/Three phase(3P)
¡á  Fail-safe(N)/Non-Fail-safe(R)
 
 
 
Protective Item
Trip Time
Descrption
Over-current

O-TIME

Is<In
Phase Loss
3 sec
.
Locked Rotor
0.5sec after elapse of dt
>2times OC setting value
   
 
 

Over-Current Setting

Current

05

0.5 ~ 6A

30

3.0 ~ 30A

60
10 ~ 60A
Starting delay time
D-TIME
1 ~30 sec

Trip time

O-TIME

0.5, 1~10 sec

Operating t-c characteristic

Over-Current

Definite

Tolerance
Current
±5%
TIME
±5%

Environment

Temperature
Operation

-20 ~60¡É

Store
-30 ~80¡É
Humidity
30~85% RH Non-condensing
Control Power
220 : 220VAC±15%, 50/60Hz
110 : 110VAC ±15%, 50/60Hz
Output relay
2-SPST
3A / 250VAC Resistive

Insulation

Between casing and circuit
Over 10M¥Ø, 500VDC
Dielectric Strenghth

Between casing and circuit

2000VAC 60Hz, 1min

Between open contacts
1000VAC 60Hz, 1min

between circuit

2000VAC 60Hz, 1min
Reset
Manual/Electrical

Installation

35mm DIN-Rail or Panel Munting